OPTITEMP TRA-V30

Resistance (RTD) compact sensor for HVAC applications with air ducts and pipes

  • Compression fitting or sliding flange connection
  • Aluminium junction box with built-in transmitter
  • -25…+200°C / -13…+390°F

OPTITEMP TRA-V30 – Standard version

Resistance (RTD) compact sensor OPTITEMP TRA-V30 – Standard version

The OPTITEMP TRA-V30 is a resistance temperature sensor (RTD) for measuring the temperature in air ducts and pipes. It features a Pt100 measuring element that is placed in the tip of the Ø 6 x 0.5 mm / 0.25 x 0.02 inch brass tube for fast response times. The compact sensor is protected by an aluminium junction box. The measuring range of this HVAC temperature sensor is -25…+200°C / -13…+390°F. The OPTITEMP TRA-V30 comes with an optional integrated transmitter providing current output (4…20 mA or 0…10 V) for the selected measuring range.

Product highlights

  • Cost-effective temperature measurement of air ducts / pipes
  • Aluminium junction box with optional integrated transmitter
  • Optional analogue output: current (4…20 mA) or voltage (0…10 V)
  • Standard or customised lengths

Typical applications

  • Temperature measurement in air conditioning and ventilation ducts
  • General HVAC applications in various industries

General information

Measurement principleResistance (RTD)
Measured mediaGases
Measuring pointPipe
Measuring insert typeNon-replaceable RTD
Measuring insert replaceableNo
RTD element type1 x Pt100, 1 x Pt1000
RTD configuration3-wire
Temperature sensor connection type optionJunction box
Sheath diametersØ6 mm / 0.23"
Process temperature-25…200°C/
-13…390°F

Communication

Analogue outputs0…10 VDC, 4…20 mA

Process connections

Compression fittingsMale:
G1/4

Links